How many wires fit in a conduit is set by the NEC Chapter 9 tables: the inside area of the conduit, the area of each wire, and a fill limit that depends on how many wires there are. Pick the EMT size, the wire size and count, and the ground, and the calculator gives the fill and the most wires of that size that fit.

freeno sign-up; it runs in your browser
0numbers sent anywhere; nothing leaves the page
1worked example, step by step
10takeoff calculators in the set

Calculator

Type the numbers. The answer updates.

Conduit fill (EMT, THHN/THWN-2)

Wire area over conduit area. Limits: 53% for one wire, 31% for two, 40% for three or more.

Embed

Put this calculator on your own site.

Free for supply houses, schools, training programs, and trade blogs. Copy the code into your page. The calculator runs in your visitors’ browsers and sends nothing anywhere.

Method

How it is calculated.

Add up the area of every wire from NEC Chapter 9, Table 5 (THHN and THWN-2 here), including the ground, and divide by the inside area of the conduit from Table 4 (EMT here). The limit from Table 1 is 53% for one wire, 31% for two, and 40% for three or more. For the most wires of one size, divide 40% of the conduit area by one wire’s area; Note 7 to Chapter 9 lets you round up when the remainder is 0.8 or more. Other conduit types and wire insulations have different areas, and long runs, many bends, or derating can call for a larger conduit than fill alone.

This is a check for a takeoff, not a substitute for reading the set. Every number in a real takeoff should come from the drawings, tied to the sheet it was read from. The handbook covers the method trade by trade.

Questions

Asked about the conduit fill calculator.

How many 12 AWG THHN wires fit in 3/4 in. EMT?

16, by the 40% limit: 40% of 0.533 sq in. is 0.2132, and 0.2132 / 0.0133 is 16.03.

How many 12 AWG THHN wires fit in 1/2 in. EMT?

9. 40% of 0.304 sq in. is 0.1216, and 0.1216 / 0.0133 is 9.14.

Does the ground count toward fill?

Yes. Every conductor in the conduit counts, including equipment grounds. A bare ground has a smaller area than an insulated one.

Why is the limit 31% for two wires?

Two round wires side by side jam more easily when pulled, so the code allows less fill for two than for one or for three or more.

Does this work for PVC or rigid conduit?

Not as is. Each conduit type has its own inside areas in Table 4; this calculator uses EMT.

Is anything I type saved or sent?

No. The calculator runs entirely in your browser.

Can a system do the whole takeoff?

That is what we build: a system that reads the uploaded set and returns the takeoff in the business’s own products and prices, with the sheet cited per line and a person reviewing before release.

Related

Other pages on this.

Talk to us

Tell us what you sell against a drawing set.

What you sell, how a set reaches you, how it gets priced, and what you want back. From that we scope a build in writing.

info@matchline.studio
Or tell us here. A person reads it and writes back.
The team that reads it is the team that builds it.